0.6/1 KV Underground Power Cable NAYY NA2XY 3x50 4x70 XLPE PVC Insulated Aluminium Conductor Multi-Core High Voltage
Basic Properties
Place of Origin:
Hebei, China
Brand Name:
Minfeng
Certification:
ISO,CE,IEC,TUV,KEMA
Model Number:
NAYY NA2XY
Trading Properties
Minimum Order Quantity:
100m
Price:
0.1-5
Payment Terms:
L/C,T/T
Supply Ability:
100KM/Week
Specifications
| Standard: | IEC 60502 | Origin: | Hebei, China |
| Voltage: | 0.6/1kv | Package: | Steel Wooden Drum |
| Core: | Aluminum | No Of Core: | 3,4 |
| Drum Length: | 500m Or As Per Request | ||
| High Light: | NAYY NA2XY underground power cable,XLPE PVC insulated aluminium conductor cable,multi-core high voltage power cable |
||
Product Description
0.6/1 KV Underground Power Cable NAYY NA2XY 3x50 4x70 XLPE PVC Insulated Aluminium Conductor Multi-Core High Voltage
Product Overview
These cables are used for electricity supply in low voltage installation systems, suitable for installation in indoors and outdoors, in cable ducts, underground, in power and switching stations, local energy distributions, and industrial plants where there is no risk of mechanical damage.
Key Specifications
Conductor Material
Aluminum
Insulation Material
XLPE
Jacket
PVC
Application
Underground
Type
Low Voltage
Rated Voltage
0.6/1KV
Core
4 core cable
Color
Black
Cable Construction
- Conductor: Hard Drawn Aluminum stranded conductor (Class 2)
- Insulation: Cross-linked polyethylene XLPE
- Filler: Non-hygroscopic material
- Binder tape: Non-hygroscopic material
- Outer sheath: Polyvinyl chloride PVC
Operating Features
- Voltage Rating Uo/U (Um): 0.6/1 (1.2)kV
- Test Voltage: 3.5kV for 5 Minutes
- Temperature Rating: -15°C to +90°C
- Maximum Short Circuit Temperature: +250°C (max 5 seconds)
- Environment temperature should be no lower than 0°C for laying the cable
- Minimum Bend Radius: Single core: 15 x overall diameter, Multi core: 12 x overall diameter
Technical Parameters
| No. of cores and nominal cross section (mm²) | Thickness of Insulation (mm) | Thickness of Sheath (mm) | Approx. overall Diameter (mm) | Approx. weight (kg/km) | Max. DC resistance of conductor(20℃) (Ω/km) | Current carrying capacity In Air(A) | Current carrying capacity In Ground(A) |
|---|---|---|---|---|---|---|---|
| 4X10 | 0.7 | 1.8 | 18.6 | 300 | 3.08 | 50 | 66 |
| 4X16 | 0.7 | 1.8 | 21.0 | 400 | 1.91 | 65 | 85 |
| 4X25 | 0.9 | 1.8 | 24.9 | 570 | 1.20 | 87 | 110 |
| 4X35 | 0.9 | 1.8 | 28.3 | 710 | 0.868 | 105 | 130 |
| 4X50 | 1.0 | 1.8 | 28.4 | 850 | 0.641 | 130 | 160 |
| 4X70 | 1.1 | 2.0 | 33.1 | 1160 | 0.443 | 165 | 195 |
| 4X95 | 1.1 | 2.1 | 37.1 | 1520 | 0.320 | 205 | 235 |
| 4X120 | 1.2 | 2.2 | 40.8 | 1898 | 0.253 | 240 | 265 |
| 4X150 | 1.4 | 2.4 | 45.2 | 2369 | 0.206 | 270 | 300 |
| 4X185 | 1.6 | 2.6 | 52.1 | 2925 | 0.164 | 315 | 340 |
| 4X240 | 1.7 | 2.8 | 57.8 | 3700 | 0.125 | 375 | 395 |
| 4X300 | 1.8 | 3.0 | 63.5 | 4580 | 0.100 | 435 | 445 |
| 4X400 | 2.0 | 3.3 | 70.9 | 5800 | 0.0778 | 510 | 510 |
Certifications & Standards
- Certificate: ISO9001/CCC
- Standard: IEC60502
- Brand Name: Minfeng OR OEM
- Place of Origin: Hebei, China