Aluminum Cable 4x50mm2 4x70mm2 4x95mm2 4x185mm2 Aluminium Power Cables 600 1000 V Multi Core Al XLPE PVC Low Voltage
Basic Properties
Place of Origin:
Hebei, China
Brand Name:
Minfeng
Certification:
ISO,CE,IEC,TUV,KEMA
Model Number:
AL/XLPE/PVC
Trading Properties
Minimum Order Quantity:
100m
Price:
0.1-5
Payment Terms:
L/C,T/T
Supply Ability:
100KM/Week
Specifications
| Insulation: | XLPE | Standard: | IEC60502 |
| Core No: | 4 | Sheath: | PVC |
| Conductor material: | Aluminum | Nominal Voltage: | 0.6/1 KV |
| High Light: | Aluminum power cable XLPE PVC,Low voltage aluminum cable multi core,Aluminium power cables 600 1000V |
||
Product Description
Aluminum Cable 4x50mm² 4x70mm² 4x95mm² 4x185mm² Aluminium Power Cables 600/1000V Multi Core Al XLPE PVC Low Voltage
Product Overview
These aluminum power cables are designed for electricity supply in low voltage installation systems, suitable for indoor and outdoor applications including cable ducts, underground installations, power stations, and industrial plants where mechanical damage is not a concern.
Key Specifications
Rated Voltage
0.6 kV, 1 kV
Conductor Material
Aluminum
Insulation Material
XLPE
Working Temperature
90°C
Jacket
PVC
Application
Underground
Type
Low Voltage
Certificate
ISO9001/CCC
Standard
IEC60502
Cable Construction
- Conductor: Hard Drawn Aluminum stranded conductor (Class 2)
- Insulation: Cross-linked polyethylene XLPE
- Filler: Non-hygroscopic material
- Binder tape: Non-hygroscopic material
- Outer sheath: Polyvinyl chloride PVC
Operating Features
- Voltage Rating Uo/U (Um): 0.6/1 (1.2)kV
- Test Voltage: 3.5kV for 5 Minutes
- Temperature Rating: -15°C to +90°C
- Maximum Short Circuit Temperature: +250°C (max 5 seconds)
- Environment temperature should be no lower than 0°C for laying the cable
- Minimum Bend Radius: Single core: 15 x overall diameter, Multi core: 12 x overall diameter
Technical Parameters
| No. of cores and nominal cross section (mm²) | Thickness of Insulation (mm) | Thickness of Sheath (mm) | Approx. overall Diameter (mm) | Approx. weight (kg/km) | Max. DC resistance of conductor(20℃) (Ω/km) | Current carrying capacity In Air(A) | Current carrying capacity In Ground(A) |
|---|---|---|---|---|---|---|---|
| 4X10 | 0.7 | 1.8 | 18.6 | 300 | 3.08 | 50 | 66 |
| 4X16 | 0.7 | 1.8 | 21.0 | 400 | 1.91 | 65 | 85 |
| 4X25 | 0.9 | 1.8 | 24.9 | 570 | 1.20 | 87 | 110 |
| 4X35 | 0.9 | 1.8 | 28.3 | 710 | 0.868 | 105 | 130 |
| 4X50 | 1.0 | 1.8 | 28.4 | 850 | 0.641 | 130 | 160 |
| 4X70 | 1.1 | 2.0 | 33.1 | 1160 | 0.443 | 165 | 195 |
| 4X95 | 1.1 | 2.1 | 37.1 | 1520 | 0.320 | 205 | 235 |
| 4X120 | 1.2 | 2.2 | 40.8 | 1898 | 0.253 | 240 | 265 |
| 4X150 | 1.4 | 2.4 | 45.2 | 2369 | 0.206 | 270 | 300 |
| 4X185 | 1.6 | 2.6 | 52.1 | 2925 | 0.164 | 315 | 340 |
| 4X240 | 1.7 | 2.8 | 57.8 | 3700 | 0.125 | 375 | 395 |
| 4X300 | 1.8 | 3.0 | 63.5 | 4580 | 0.100 | 435 | 445 |
| 4X400 | 2.0 | 3.3 | 70.9 | 5800 | 0.0778 | 510 | 510 |
Packaging & Shipping
Packing
- Steel wooden drum (fumigation)
- Cable length in each drum: 1000m/2000m or as per actual cable length requirements
- Drum size: As per cable length and container size
In order to quote you accurate price, kindly tell us your needed cable length quantity. Larger quantity, more discount benefit ready for you!
Shipping Port
Tianjin, Qingdao, or other ports as per your requirements.
Sea Freight
FOB/C&F/CIF quotation are all available.
For some countries such as Africa countries, middle east countries, our sea freight quotation is much cheaper than clients get from local shipping agency.
Overall Rating
5 star
100%
4 star
0
3 star
0
2 star
0
1 star
0
All Reviews
-
CWe’ve integrated these fiber optic cables into our latest data center project. The attenuation levels are remarkably low, exceeding our performance benchmarks.