AMCL 12 KV 24 KV Medium Voltage Cable with Aluminum Conductor and Polypropylene Insulation for Industrial Use
| Packing Style: | Steel/ Wooden Drum | Sheath: | HDPE |
| Insulation: | Pp | Standard: | HD 620 S3 / SS 424 14 20 |
| Temperature: | -20 °C-90℃ | Range Of Application: | Industrial |
| Conductor: | Aluminum | Cable Sample: | Free |
AMCL is a halogen-free, three-core cable featuring circular aluminum conductors, PP-TPE insulation, copper screen, and a sheath of recycled polyethylene with an outer layer of HDPE. Designed for industrial applications with excellent UV resistance and waterproof properties.
- Conductor Material: Aluminum
- Conductor Shape: Round, stranded
- Insulation: PP (polypropylene)
- Outer Sheath: HDPE
- Color: Black
- Conductor Flexibility: Class 2
- Halogen Free: Yes
- Screen: Concentric copper
- Number of Cores: 3
- Nominal Insulation Thickness: 3.4 mm
- Operating Voltage: 12 kV
- Rated Voltage Uo/U (Um): 7 / 12 kV
- Minimum Installation Temperature: -20°C
- Maximum Operating Temperature: 90°C
- Bending Factor (installed): 8 (xD)
- Bending Factor (laying): 12 (xD)
- Rip Cord: Yes
- Short-circuit Max. Conductor Temperature: 250°C
- U.V Resistance: Good
- Water Proof: Good
| Model | Conductor Cross-section (mm²) | Screen Section (mm²) | Nominal Outer Diameter (mm) |
|---|---|---|---|
| AMCL 12 kV 3x50/16 | 50 | 16 | 42.0 |
| AMCL 12 kV 3x95/25 | 95 | 25 | 50.0 |
| AMCL 12 kV 3x150/25 | 150 | 25 | 56.0 |
| AMCL 12 kV 3x240/35 | 240 | 35 | 65.0 |
| AMCL 24 kV 3x50/16 | 50 | 16 | 51.0 |
| AMCL 24 kV 3x95/25 | 95 | 25 | 59.0 |
| AMCL 24 kV 3x150/25 | 150 | 25 | 66.0 |
| AMCL 24 kV 3x240/35 | 240 | 35 | 75.0 |
| AMCL 24 kV 3x300/35 | 300 | 35 | 80.0 |
AMCL is manufactured and tested according to HD 620 S3 / SS 424 14 20. The cable can be loaded according to SS 424 14 20. The conductor meets the requirements for IEC 60228 class 2.
Note: The sheath opens with a rip cord and is marked with type, manufacturer, year+month, and metre marking. AMCL is produced with low carbon aluminum and is easy to recycle. Joint and cable terminations are standard materials from accessory manufacturers.
Maximum pulling force using cable stocking: F (N) = 5 x D²
-
MIn an industry plagued by shortages, this manufacturer’s ability to maintain a steady lead time is a massive asset to our supply chain.