logo

Aluminum Power Cable AXMK PE XLPE Insulated and PE Sheathed Power Cables Rated Voltage 0.6/1 KV

Basic Properties
Place of Origin: China
Brand Name: Minfeng
Certification: ISO,CE,IEC,TUV,KEMA
Model Number: AXMK-PE
Trading Properties
Minimum Order Quantity: 100m
Price: 0.1-5
Payment Terms: L/C,T/T
Supply Ability: 100KM/Week
Specifications
Standard Compliance: HD 603 S1, SFS 4879 Insulation: XLPE
Sheath Mark: Ink Printing Or Embossing Outer Sheath: PE
Temperature Range: -15°C-90°C Minimum Order: 100 M
Product Description

Key attributes


Rated Voltage
0.6/1kv
Size
16-240mm2
Conductor Material
Aluminum
Insulation Material
XLPE
Working Temperature
-15°C-90°C
Jacket
PE
IP Level
/
Application
Industrial
Rated Current
/
Type
Low Voltage
Place of Origin
Hebei, China
Model Number
AXMK-PE
Brand Name
Minfeng
Product name
AXMK-PE
Standard
HD 603 S1, SFS 4879
Conductor
Aluminum
Insulation
XLPE
Nominal voltage
0.6/1kv
Sheath
PE
Product Description
Aluminum Power Cable AXMK PE XLPE Insulated and PE Sheathed Power Cables Rated Voltage 0.6/1 KV 0



APPLICATION
In earth, ducts, on support brackets, in dry and wet conditions etc., where one does not expect mechanical damages and the cables are not exposed to the mechanical tensile strain. In urban networks, industrial plants, electric power plants and other electricity consumers and for connection of control devices in industry, traffic etc.
Construction
Conductors: Al, class 1 or class 2 according to EN 60228, annealed Insulation: XLPE compound Bedding: Extruded filling compound or plastic tape Outer sheath: PE compound, UV resistant
Tehnical characteristics CPR class: Fca Test voltage: 4 kV AC, 50 Hz, 5 min. Rated voltage: 0,6/1 kV AC (1,5 kV DC) Min. bending radius: multicore- 10D, D – overall diameter Min. laying temperature: -15°C Max. conductor operating temperature: 90°C Max. short-circuit temperature: 250°C Environment operating temp.: -35°C to +3 Core marking: acc. to HD 308 S2 4-core: Green/Yellow, Brown, Black, Gray or Blue, Brown, Black, Gray 5-core: Green/Yellow, Blue, Brown, Black, Gray or Blue, Brown, Black, Gray, Black Or by customer request
Specification
NOMINAL CROSS SECTIONAL AREA
CONDUCTOR SHAPE
NOMINAL THICKNESS OF INSULATION
NOMINAL OVERALL DIAMETER
ALUMINIUM WEIGHT
NOMINAL WEIGHT
mm²
mm
mm
mm
kg/km
kg/km
1×16
RE
0.7
9.5
46
122
1×25
RE
0.9
11.9
73
175
1×35
RM
0.9
13
102
206
1×50
RM
1
14.9
145
267
1×70
RM
1.1
17
203
358
1×95
RM
1.1
18.9
276
451
1×120
RM
1.2
20.7
348
546
1×150
RM
1.4
22.7
435
655
1×185
RM
1.6
25.1
537
800
1×240
RM
1.7
27.6
696
987
1×300
RM
1.8
31.9
870
1324
1×400
RM
2
34.9
1160
1640
1×500
RM
2.2
39.3
1450
2030
1×630
RM
2.4
44.1
1827
2400
4×16
RE
0.7
18.3
185
596
4×25
SM
0.9
21.1
290
509
4×35
SM
0.9
23.4
406
653
4×50
SM
1
26.4
580
832
4×70
SM
1.1
30.4
812
1118
4×95
SM
1.1
34.1
1102
1465
4×120
SM
1.2
38.1
1392
1837
4×150
SM
1.4
42.1
1740
2250
4×185
SM
1.6
46.6
2146
2807
4×240
SM
1.7
52.2
2784
3603
4×300
SM
1.8
55.9
3480
4223
5×10
RE
0.7
17.8
145
422
5×16
RE
0.7
20
232
544
5×25
SM
0.9
22.9
363
606
5×35
SM
0.9
25.7
507.8
807
5×50
SM
1
30.1
725
1032
5×70
SM
1.1
35.1
1015
1404
5×95
SM
1.1
38.1
1380
1800
5×120
SM
1.2
40.3
1740
2320
5×150
SM
1.4
47.4
2175
2900
5×185
SM
1.6
52.7
2682.5
3352.5
5×240
SM
1.7
59.4
3480
4350