آخرین اخبار شرکت در مورد How Offshore Wind Power Crosses the Sea to Reach Your City

November 6, 2026

How Offshore Wind Power Crosses the Sea to Reach Your City


From the shore, offshore wind turbines look like a row of distant white windmills. But when the blades start turning, the electricity they make does not “fly” back to the city—and certainly not with one cable running from every turbine to the land.

The real path is hidden inside the tower, the offshore substation, and the seabed:

Collect → Step up → Cross the sea → Landfall → Onshore grid

How far the sea is, and how large the wind farm is, decides whether the link uses AC or DC.


1. Collecting Power From Many Turbines

Wind pushes the blades, the drive train and generator convert mechanical energy into electricity. Different turbine models vary in design, but the output usually passes through converters and small step-up units to reach the collection voltage the farm needs.

Multiple turbines are then linked by array cables​ in strings, feeding into the offshore substation.

Typical modern array voltages:

  • Legacy farms: 33 kV AC
  • New large farms: 66 kV AC
  • Future ultra-large farms: 132 kV array systems in planning

Raising array voltage reduces current, cuts resistive loss, and lets each cable string serve more turbines.


2. The Offshore Substation: A Power Hub at Sea

Think of the offshore substation as a “power transfer station” built on the water.

It gathers the distributed output from all turbine strings, then steps the voltage up—typically to 132 kV, 220 kV, or 345 kV. For the same power, higher voltage means lower current, which reduces heat loss in the export cable.

Only after this stage is the power ready for the cross-sea journey.


3. Subsea Export Cables Are Not “Wires Soaked in Water”

An export cable is a engineered multi-layer system:

Layer

Function

Conductor

Carries current (copper or aluminum)

XLPE insulation

Withstands high voltage, marine thermal cycles

Water barrier

Blocks longitudinal water penetration

Armor (SWA/STA)

Resists tension, abrasion, anchors, fishing gear

Outer sheath

Anti-corrosion, anti-biofouling, UV resistant

Cable-lay vessels place the cable on the seabed. Critical sections are buried 1–3 m deep or protected with rock dumping to reduce damage from anchors and trawl gear.

After landfall, the cable enters an onshore substation and feeds the regional load center.


4. HVAC or HVDC? Distance Decides

Near shore, moderate capacity → HVAC

  • Simple, mature, grid-friendly
  • But AC submarine cables act like long capacitors
  • Charging current grows with length
  • Practical economic limit: ~80–100 km without heavy reactive compensation

Far shore, large capacity → HVDC (VSC/flexible DC)

  • Offshore converter: AC → DC
  • DC export cable to shore
  • Onshore converter: DC → AC grid
  • No capacitive charging penalty
  • Common voltages: ±320 kV to ±525 kV
  • Best for 100+ km routes and multi-terminal offshore grids

The converter stations add cost, but they remove the distance limitation and give better grid control.


5. Why Offshore Transmission Is Hard

The challenge is not only “the sea is wide.”

  • Salt spray, humidity, and corrosion
  • Typhoons, waves, and tidal movement
  • Seabed mobility and burial conditions
  • Anchor strikes and fishing-gear interaction
  • Fault location and repair are slow—vessels, weather windows, jointing, reburial

That is why route selection, redundancy, online monitoring (DTS/DAS via integrated fiber), and maintenance vessels must be planned before construction starts.

Subsea cables are often only ~8–10% of CAPEX, but drive the majority of unplanned downtime and insurance claims.


6. Where Minfeng Cable Fits in the Chain

While full HVDC export cables are a specialist subsea scope, the onshore and platform-side electrical system still depends on rugged, standards-compliant cabling:

  • XLPE insulated SWA/STA armored power cables (up to 35 kV)​ for collection, platform, and onshore tie-in
  • LSZH fire-resistant cables​ with 3-hour circuit integrity for evacuation, control, and safety systems
  • ACSR and 110 kV class conductors​ for grid connection and step-up interfaces
  • 1500 V DC renewable cables​ for hybrid wind-solar platforms
  • Built to IEC, TÜV, CCC, and project-specific specs

For offshore-adjacent projects, the rule is simple: the cable is the most exposed asset in the whole system. Armor, insulation, and certification are not optional.


Summary

Offshore wind does not reach the city by magic. It moves through:

Turbine → 66 kV array cable → offshore substation → HVAC or HVDC export → seabed → onshore grid

The further the farm, the more the cable—not the turbine—decides project reliability and cost.