3-30kV Rated Voltage Flexible Mining Rubber Cable for Semiflexible Installation German Standard DIN VDE 0250-813 Medium Voltage MV
| Application: | শিল্প, খনির | Insulation material: | রাবার |
| Rated Voltage: | 3-30kv | Outer Sheath Material: | সিন্থেটিক ইলাস্টোমার যৌগ |
| Model Name: | F-(N)TSCGEWOEU | Conductor Type: | ইলেক্ট্রোলাইটিক তামা |
| Corporation: | মিনফেং গ্রুপ |
Flexible mining rubber cable designed for semiflexible installation according to German standards, suitable for medium voltage applications in demanding industrial and mining environments.
| Rated Voltage | 3-30kV |
| Conductor Material | Electrolytic copper |
| Insulation Material | EPR |
| Working Temperature | -40°C to +80°C |
| Jacket Material | Synthetic elastomer compound |
| Application | Industrial, Mining |
| Type | Medium Voltage |
| Model Number | F-(N)TSCGEWOEU |
| Standard | DIN VDE 0250-813 |
For laying alongside conveyor belts (including shiftable units) and on material handling equipment. Suitable for continuous movement applications such as cable booms or connections between upper and lower cars, and for connection of submersible pump units.
- Type Designation: F-(N)TSCGEWOEU
- Standard: Based on DIN VDE 0250-813
- Certifications: Fire Certificate of Russian Federation, GOST -R/-K/-B
- Conductor: Electrolytic copper, not tinned, very finely stranded (class 5)
- Insulation: PROTOLON, Basic material: EPR, Compound type: Special compound
- Electrical Field Control: Inner and outer layer of semiconductive rubber compound
- Core Identification: Natural coloring with black semiconductive rubber with white digits 1 to 3
- Core Arrangement: Three main conductors laid-up, with protective-earth conductor split into 3 in outer interstices
- Inner Sheath: Basic material: EPR, Compound type: Special compound
- Outer Sheath: Basic material: Synthetic elastomer compound, Color: Red
- Resistance to Oil: According to DIN EN 60811-404 and DIN VDE 0473-811-404
- Weather Resistance: Unrestricted use outdoors and indoors, resistant to ozone, UV and moisture
- Water Resistance: According to HD 2216
- Max. Permissible Temperature at Conductor: 90°C
- Max. Short Circuit Temperature: 250°C
- Ambient Temperature (Fixed Installation): -50°C to +80°C
- Ambient Temperature (Flexible Operation): -35°C to +80°C
- Max. Tensile Load on Conductor: 20 N/mm²
- Max. Tensile Load During Acceleration: Up to 30 N/mm²
- Torsional Stress: ± 25°/m
- Min. Bending Radius: According to DIN VDE 0298 part 3
- Min. Distance with S-type Directional Changes: 20 x D (D = cable diameter)
- Travel Speed: Gantry (reeling operation): no restriction. For speeds beyond 240 m/min
-
GThe LSZH (Low Smoke Zero Halogen) properties of these cables are exactly as advertised. They performed exceptionally well during our fire safety compliance audit.
-
IOur field technicians have specifically requested this brand because the cable is easy to strip and pull through conduits, saving us significant man-hours on-site.